Skip to main content

IEC 62271-200:2021

Current Date published:

High-voltage switchgear and controlgear - Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV

IEC 62271-200:2021 is applicable to prefabricated metal‑enclosed switchgear and controlgear assemblies designed for:
– alternating current;
– rated voltages above 1 kV and up to and including 52 kV;
– service frequencies up to and including 60 Hz;
– indoor and outdoor installation.
The assembly can include air-insulated and/or fluid-filled compartments.
This third edition cancels and replaces the second edition published in 2011. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) clause numbering aligned with IEC 62271‑1:2017, including the adoption of the subclause names of Clause 3;
b) in Clause 3 specific definitions are added for "in service", "normal operating condition" and "normal use";
c) internal arc testing on pole-mounted switchgear is taken out of this document, as it is now covered by the specific standard IEC 62271‑214:2019;
d) a more precise description of earthing circuit is given with the inclusion of ratings and test requirements;
e) number of mechanical tests on interlocks is reduced for type testing; a more precise description of forces to apply during type testing is given (refer to 7.102);
f) resistance measuring on main circuit is only needed before continuous current tests (as reference for routine tests) and no longer needed after this continuous current test. Rationale for this deletion is that this measured resistance does not mean anything; as the temperature rise test was just finished, a new temperature rise test will not give new information;
g) IEC 62271-100:2021, IEC 62271-103:2021, IEC 62271-105:2021 and IEC 62271-106:2021 are referred to in the document;
h) IEC 62271‑107:2019 and IEC IEEE 62271‑37‑013:2015 are also considered in 7.101.2;
i) a more precise description of LSC category is given with the inclusion of an explanatory flowchart (Annex D);
j) examples not covered by the IAC test are transferred from Clause 6 to 9.103;
k) the term "assembly" is defined in Clause 3 and used as synonym for "metal-enclosed switchgear and controlgear" in this document;
l) "metallic" is replaced by "metal" where applicable;
m) 6.105 is now covered by 7.7;
n) a 1 s rule was introduced for Criterion 4 during IAC tests regarding hot gases versus glowing particles as cause of ignition;
o) a more precise description of internal arc tests for switchgear with protrusions is given in Annex A.

Get this standard Prices exclude GST
PDF ( Single user document)
$869.00 NZD
HardCopy
$826.00 NZD
Networkable PDF
Price varies
Preview only close
Prev {{ page }}/ {{ numPages }} Next
Preview only close
Prev {{ page }}/ {{ numPages }} Next

Keep me up-to-date

Sign up to receive updates when there are changes to this standard

Related Information

Similar Standards

  • AS/NZS 60265.1:2001

    High-voltage switches - Switches for rated voltages above 1 kV and less than 52 kV

  • BS 6626:2010

    Maintenance of electrical switchgear and controlgear for voltages above 1 kV and up to and including 36 kV. Code of practice

  • BS 6867:2013

    Maintenance of electrical switchgear and controlgear for voltages above 36 kV. Code of practice

  • BS EN 50052:2016

    High-voltage switchgear and controlgear. Gas-filled cast aluminium alloy enclosures

Preview only close
Prev {{ page }}/ {{ numPages }} Next
Preview only close
Prev {{ page }}/ {{ numPages }} Next

IEC 62271-200:2021

Get this standard Prices exclude GST
PDF ( Single user document)
$869.00 NZD
HardCopy
$826.00 NZD
Networkable PDF
Price varies

Request to add this standard to your subscription

IEC 62271-200:2021

Price varies
Online library subscription

Your organisation’s Account Administrator must approve a request to add a standard to your subscription.

You may add a comment to the administrator below.

Cancel