IEC 60947-4-1:2009

Superseded Date published:

Warning: Superseded Standard. This document has been replaced by:

IEC 60947-4-1:2018 RLV

Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters

IEC 60947-4-1:2009 applies to the types of equipment whose main contacts are intended to be connected to circuits the rated voltage of which does not exceed 1 000 V a.c. or 1 500 V d.c. Starters and/or contactors dealt with in this standard are not normally designed to interrupt short-circuit currents. Therefore, suitable short-circuit protection forms part of the installation but not necessarily of the contactor or the starter. This third edition replaces the second edition published in 2000 and its Amendments 1 (2002) and 2 (2005). It is a technical revision. This edition includes the following significant technical changes with respect to the previous edition (2000) and its Amendments 1 (2002) and 2 (2005):
- deletion of the test at -5 °C and +20 °C for thermal overload relays that are not compensated for ambient air temperature;
- addition of conditions of the tests according to Annex Q of IEC 60947-1;
- EMC tests: clarification of acceptance criteria and alignment with IEC 60947-1 for fast transient severity level;
- Annex B, test for Icd: modification of the duration of the dielectric test voltage from 5 s to 60 s;
- Annex B, electrical durability: improvement of the statistical aspects;
- Annex H: clarification and introduction of new extended functions within electronic overload relays;
- Annex K, procedure to determine data for electromechanical contactors used in functional safety applications: creation of this new annex. This standard shall be read in conjunction with IEC 60947-1, Low voltage switchgear and controlgear - Part 1: General rules. The provisions of the general rules are applicable to this standard, where specifically called for.

This publication shall be read in conjunction with IEC 60947-1 :2007.

Get this standard Prices exclude GST
PDF ( Single user document)
$1,041.75 NZD
HardCopy
$987.75 NZD
Networkable PDF
Price varies
Preview only close
Prev {{ page }}/ {{ numPages }} Next
Preview only close
Prev {{ page }}/ {{ numPages }} Next

Keep me up-to-date

Sign up to receive updates when there are changes to this standard

Related Information

Similar Standards

  • AS/NZS 3190:2016


    Approval and test specification - Residual current devices (current-operated earth-leakage devices)

  • AS/NZS 3190:2016 A1


    Approval and test specification - Residual current devices (current operated earth-leakage devices)

  • AS/NZS 3190:2016 A2

    Approval and test specification – Residual current devices (current operated earth-leakage devices)

  • AS/NZS 4763:2011


    Safety of portable inverters

Preview only close
Prev {{ page }}/ {{ numPages }} Next
Preview only close
Prev {{ page }}/ {{ numPages }} Next

IEC 60947-4-1:2009

Get this standard Prices exclude GST
PDF ( Single user document)
$1,041.75 NZD
HardCopy
$987.75 NZD
Networkable PDF
Price varies

Request to add this standard to your subscription

IEC 60947-4-1:2009

Price varies
Online library subscription

Your organisation’s Account Administrator must approve a request to add a standard to your subscription.

You may add a comment to the administrator below.

Cancel